PHLTD MDR-10, 20W product dimension diagram | ||||||||
PHLTD MDR-10W | ||||||||
PHLTD MDR-10, 20W Product Parameter Table | ||||||||
model | MDR-10 | MDR-20 | ||||||
DC Voltage | 5V | 12V | 15V | 24V | 5V | 12V | 15V | 24V |
Rated current | 2A | 0.84A | 0.67A | 0.42A | 3A | 1.67A | 1.34A | 1A |
rated power | 10W | 10W | 10W | 10W | 15W | 20W | 20W | 24W |
Voltage accuracy | ±5% | ±3% | ±3% | ±2% | ±2% | ±1% | ±1% | ±1% |
Working current | 0.33A/110VAC 0.21A/230VAC | 0.55A/110VAC 0.35A/230VAC |
output | voltage | 5V | 12V | 15V | 24V |
Ripple and noise ① | <80mV | <120mV | <120mV | <150mV | |
Voltage regulation range | ±10% | ||||
Line Regulation | ±1% | ||||
Load Regulation | ±5% | ±3% | ±3% | ±2% | |
input | Start, rise, hold time | 1000ms、30ms、25ms :110VAC 500ms、30ms、120ms :220VAC | |||
Voltage range/frequency | 85-264VAC 47HZ-63Hz(120VDC-370VDC) | ||||
Efficiency (typical) ② | >77% | >81% | >81% | >84% | |
Impulse current | 110VAC 35A 220VAC 70A | ||||
Protective characteristics | overload protection | ≥ 105% -150% Type: Protection mode: Hiccup mode Automatic recovery after abnormal conditions are lifted | |||
Overvoltage protection | When the output voltage is greater than 135%, turn off the output and automatically recover after the abnormal conditions are resolved | ||||
environment | Working temperature and humidity | -20℃~+70℃;20%~90RH | |||
Storage temperature and humidity | -40℃~+85℃;10%-95RH | ||||
secure | pressurization | Input output: 3KVAC lasting for 1 minute | |||
Isolation resistor | Input output, input housing, output housing: 500VDC/100M Ω | ||||
other | size | 22.5*90*100mm | |||
notes | ① Ripple and noise measurement method: Use a 12 “twisted pair cable, with terminals connected in parallel with 0.1uF and 47uF capacitors, and measure at a bandwidth of 20MHz. ② Efficiency is tested at an input voltage of 230VAC, rated load, and an ambient temperature of 25 ℃. Accuracy: including setting error, linear adjustment rate, and load adjustment rate. Linear adjustment rate testing method: Test from low voltage to high voltage under rated load Load adjustment rate testing method: from 0% to 100% of rated load. The startup time is measured in a cold start state, and rapid and frequent shutdowns may increase the startup time, When the operating altitude is above 2000 meters, the operating environment temperature needs to be reduced by 5 ℃/1000 meters |
MDR-60W Product Dimensional Drawing | ||||||||
MDR-60W | ||||||||
MDR-60W Product Parameter Table | ||||||||
model | MDR-40 | MDR-60 | ||||||
DC Voltage | 5V | 12V | 15V | 24V | 5V | 12V | 15V | 24V |
Rated current | 8A | 3.3A | 2.67A | 1.67A | 12A | 5A | 4A | 2.5A |
rated power | 40W | 40W | 40W | 40W | 60W | 60W | 60W | 60W |
Voltage accuracy | ±2% | ±1% | ±1% | ±1% | ±2% | ±1% | ±1% | ±1% |
Working current | 1.1A/110VAC 0.7A/230VAC | 1.8A/110VAC 1A/230VAC |
output | voltage | 5V | 12V | 15V | 24V |
Ripple and noise ① | <80mV | <120mV | <120mV | <150mV | |
Voltage regulation range | ±10% | ||||
Line Regulation | ±1% | ||||
Load Regulation | ±2% | ±1% | ±1% | ±1% | |
input | Start, rise, hold time | 1000ms、30ms、25ms :110VAC 500ms、30ms、120ms :220VAC | |||
Voltage range/frequency | 85-264VAC 47HZ-63Hz(120VDC-370VDC) | ||||
Efficiency (typical) ② | >77% | >81% | >81% | >84% | |
Impulse current | 110VAC 35A 220VAC 70A | ||||
Protective characteristics | overload protection | ≥ 105% -150% Type: Protection mode: Hiccup mode Automatic recovery after abnormal conditions are lifted | |||
Overvoltage protection | When the output voltage is greater than 135%, turn off the output and automatically recover after the abnormal conditions are resolved | ||||
environment | pressurization | Input output: 3KVAC lasting for 1 minute | |||
Isolation resistor | Input output, input housing, output housing: 500VDC/100M Ω | ||||
other | size | 40*90*100mm | |||
notes | ① Ripple and noise measurement method: Use a 12 “twisted pair cable, with terminals connected in parallel with 0.1uF and 47uF capacitors, and measure at a bandwidth of 20MHz. ② Efficiency is tested at an input voltage of 230VAC, rated load, and an ambient temperature of 25 ℃. Accuracy: including setting error, linear adjustment rate, and load adjustment rate. Linear adjustment rate testing method: Test from low voltage to high voltage under rated load Load adjustment rate testing method: from 0% to 100% of rated load. The startup time is measured in a cold start state, and rapid and frequent shutdowns may increase the startup time, When the operating altitude is above 2000 meters, the operating environment temperature needs to be reduced by 5 ℃/1000 meters |
MDR-100W Product Dimensional Drawing | ||||
MDR-100W | ||||
MDR-100W Product Parameter Table | ||||
model | MDR-100 | |||
output | DC Voltage | 12V | 24V | 48V |
Rated current | 8.3A | 4.1A | 2A | |
rated power | 100W | 100W | 100W | |
Ripple and noise ① | 120mVp-p | 150mVp-p | 200mVp-p | |
Voltage regulation range | ±10% | |||
Voltage accuracy | ±2.0% | ±1.0% | ||
Line Regulation | <±0.5% | |||
Load Regulation | <±1.5% | <±0.5% | <±0.5% | |
input | Voltage range/frequency | 85-264VAC 47Hz-63Hz(120VDC-370VDC | ||
Efficiency (typical) ② | >83% | >86% | >87% | |
Working current | <1.3A 115VAC <0.8A 230VAC | |||
Impulse current | 115VAC 30A,220VAC 60A | |||
Start, rise, hold time | 200ms、50ms、20ms :220VAC | |||
Protective characteristics | overload protection | ≥ 105% -150% Type: Constant current output+VO drops to undervoltage point Cut off output reset: Power on again | ||
Short circuit protection | +Vo drops to undervoltage point and closes output | |||
environment | Working temperature and humidity | -10℃~+50℃;20%~90RH | ||
Storage temperature and humidity | -20℃~+85℃;10%-95RH | |||
pressurization | Input output: 1.5KVAC Input housing: 1.5KVAC Output Housing: 0.5KVAC for 1 minute |
|||
Leakage current | <5mA at 1.5KVAC input output | |||
Leakage current | <1mA when input-output 220VAC | |||
Isolation resistor | Input output, input housing, output housing: 500VDC/100M Ω | |||
other | size | 56*110*90mm | ||
notes | ① Ripple and noise measurement method: Use a 12 “twisted pair cable, with terminals connected in parallel with 0.1uF and 47uF capacitors, and measure at a bandwidth of 20MHz. ② Efficiency is tested at an input voltage of 230VAC, rated load, and an ambient temperature of 25 ℃. Accuracy: including setting error, linear adjustment rate, and load adjustment rate. Linear adjustment rate testing method: Test from low voltage to high voltage under rated load Load adjustment rate testing method: from 0% to 100% of rated load. The startup time is measured in a cold start state, and rapid and frequent shutdowns may increase the startup time, When the operating altitude is above 2000 meters, the operating environment temperature needs to be reduced by 5 ℃/1000 meters |
High efficiency: Equipped with advanced power conversion technology, it ensures that the power supply maintains high efficiency during the conversion process, reduces energy waste, and reduces equipment operating costs.
Low standby power consumption: The wattage consumption of idle standby is lower than the industry standard, reducing power consumption in standby mode, in line with the modern concept of energy conservation and environmental protection.